Procedure for Calculating Distance of Actuator from Hot Valve

The purpose of this post is to assist in determining the proper distance of a Kinetrol actuator from a hot valve.

In many situation, valves are put inline with a hot process media flowing through the piping system. In these situations, careful consideration must be taken to avoid over temperature exposure of the Kinetrol actuator via conductive or radiant heat.

The following formulae will assist in giving you data to calculate the safe distance between hot valve and actuator.


For steel RHS mount kits, standard (80°C Max.) actuators In ambient 50°C air. 



If you need assistance, or have any concerns about properly distancing the actuator from your process, it's always best to consult with the experts at Kinetrol USA. They're just a phone call away.